Alright students, welcome to this deep dive into one of the most crucial concepts in Alternating Current (AC) circuits:
Power in AC circuits and the Power Factor. While DC circuits have a straightforward definition of power (P = VI = IยฒR = Vยฒ/R), AC circuits introduce a layer of complexity due to the time-varying nature of voltage and current, and more importantly, the phase difference that can exist between them. This concept is fundamental for both your CBSE board exams and, especially, for cracking the IIT JEE Main & Advanced.
---
###
1. Instantaneous Power in AC Circuits
Let's begin with the basics. In any electrical circuit, the
instantaneous power $P(t)$ at any moment $t$ is given by the product of the instantaneous voltage $V(t)$ across the element and the instantaneous current $I(t)$ flowing through it.
So,
$P(t) = V(t) cdot I(t)$.
Consider a general AC circuit where the instantaneous voltage is given by:
$V(t) = V_0 sin(omega t)$
And the instantaneous current is given by:
$I(t) = I_0 sin(omega t - phi)$
Here, $V_0$ and $I_0$ are the peak values of voltage and current, respectively, $omega$ is the angular frequency, and $phi$ is the phase difference between the voltage and current. A positive $phi$ indicates that the current *lags* the voltage (typically in inductive circuits), and a negative $phi$ indicates that the current *leads* the voltage (typically in capacitive circuits).
Substituting these into the power equation:
$P(t) = (V_0 sin(omega t)) (I_0 sin(omega t - phi))$
$P(t) = V_0 I_0 sin(omega t) sin(omega t - phi)$
Using the trigonometric identity $2 sin A sin B = cos(A-B) - cos(A+B)$:
$P(t) = frac{V_0 I_0}{2} [ cos(omega t - (omega t - phi)) - cos(omega t + (omega t - phi)) ]$
$P(t) = frac{V_0 I_0}{2} [ cos(phi) - cos(2omega t - phi) ]$
This expression for instantaneous power tells us a few things:
1. It is a time-varying quantity, oscillating at
twice the frequency of the applied voltage or current ($2omega$).
2. It has a constant term, $frac{V_0 I_0}{2} cos(phi)$, and a time-varying term, $-frac{V_0 I_0}{2} cos(2omega t - phi)$.
---
###
2. Average Power in AC Circuits (Real Power)
In AC circuits, especially for practical applications, we are usually more interested in the
average power consumed over a complete cycle, rather than the instantaneous power. This is because the instantaneous power oscillates, and over a full cycle, the energy stored and released by reactive components (inductors and capacitors) averages out to zero.
To find the average power, we integrate the instantaneous power over one full cycle ($T = 2pi/omega$) and divide by the time period $T$:
$P_{avg} = frac{1}{T} int_0^T P(t) dt$
$P_{avg} = frac{1}{T} int_0^T frac{V_0 I_0}{2} [ cos(phi) - cos(2omega t - phi) ] dt$
$P_{avg} = frac{V_0 I_0}{2T} left[ int_0^T cos(phi) dt - int_0^T cos(2omega t - phi) dt
ight]$
Let's evaluate the two integrals separately:
1. $int_0^T cos(phi) dt = cos(phi) int_0^T dt = cos(phi) [t]_0^T = T cos(phi)$
2. $int_0^T cos(2omega t - phi) dt$: The integral of a cosine function over a full period (or multiple periods) is always zero. Since $2omega T = 2omega (2pi/omega) = 4pi$, which is two full periods, this integral evaluates to zero.
Therefore,
$P_{avg} = frac{V_0 I_0}{2T} [ T cos(phi) - 0 ]$
$P_{avg} = frac{V_0 I_0}{2} cos(phi)$
Now, we know that the RMS (Root Mean Square) values of voltage and current are $V_{rms} = V_0/sqrt{2}$ and $I_{rms} = I_0/sqrt{2}$.
So, $V_0 = sqrt{2} V_{rms}$ and $I_0 = sqrt{2} I_{rms}$.
Substituting these into the average power equation:
$P_{avg} = frac{(sqrt{2} V_{rms}) (sqrt{2} I_{rms})}{2} cos(phi)$
$P_{avg} = V_{rms} I_{rms} cos(phi)$
This is the most important formula for average power in an AC circuit. It is also often called
Real Power or
True Power because it represents the actual power dissipated or converted into useful work (e.g., heat in a resistor, mechanical work in a motor). Its unit is
Watts (W).
---
###
3. The Power Factor (cos $phi$)
The term $cos(phi)$ in the average power equation,
$P_{avg} = V_{rms} I_{rms} cos(phi)$, is called the
power factor.
The
power factor is defined as the cosine of the phase difference ($phi$) between the voltage and current in an AC circuit.
Power Factor (PF) = $cos(phi)$
It is a dimensionless quantity that can range from 0 to 1. It tells us how effectively the apparent power is being converted into useful work.
*
If $phi = 0^circ$ (purely resistive circuit), then $cos(phi) = cos(0^circ) = 1$. This is called
unity power factor. In this case, $P_{avg} = V_{rms} I_{rms}$, meaning all the apparent power is consumed as real power. This is the ideal scenario for power utilization.
*
If $phi = pm 90^circ$ (purely inductive or capacitive circuit), then $cos(phi) = cos(pm 90^circ) = 0$. This is called
zero power factor. In this case, $P_{avg} = 0$, meaning no real power is consumed over a full cycle. The reactive components merely store and release energy, returning it to the source.
For a series RLC circuit, the impedance is $Z = sqrt{R^2 + (X_L - X_C)^2}$, and the phase angle is given by $ an(phi) = frac{X_L - X_C}{R}$.
From the impedance triangle (or using trigonometry), we can also express the power factor as:
$cos(phi) = frac{R}{Z}$
This formula is extremely useful for calculating the power factor in RLC circuits.
---
###
4. Types of Power: Apparent, Real, and Reactive Power
To fully understand power in AC circuits, it's essential to distinguish between three types of power:
1.
Apparent Power (S):
* This is the product of the RMS voltage and RMS current, without considering the phase difference.
* $S = V_{rms} I_{rms}$
* Its unit is
Volt-Ampere (VA).
* It represents the total power that *appears* to be flowing in the circuit from the source. It is the maximum possible power that can be delivered to the load.
2.
Real Power (P) (also called True Power or Active Power):
* This is the actual power consumed by the circuit and converted into other forms of energy (heat, light, mechanical work).
* $P = V_{rms} I_{rms} cos(phi) = S cos(phi)$
* Its unit is
Watts (W).
* This is the power measured by a wattmeter.
3.
Reactive Power (Q):
* This is the power that continuously oscillates back and forth between the source and the reactive components (inductors and capacitors) in the circuit. It is not consumed by the circuit but is necessary to build up and maintain the magnetic and electric fields in these components.
* $Q = V_{rms} I_{rms} sin(phi) = S sin(phi)$
* Its unit is
Volt-Ampere Reactive (VAR).
* Inductive loads consume lagging reactive power, while capacitive loads supply leading reactive power.
These three powers are related geometrically through the
Power Triangle:
The Power Triangle |
|---|
Imagine a right-angled triangle where:
- The hypotenuse represents the Apparent Power (S).
- The adjacent side represents the Real Power (P).
- The opposite side represents the Reactive Power (Q).
The angle between the Real Power (P) and Apparent Power (S) is the phase angle $phi$.

|
Mathematical Relations |
- $S^2 = P^2 + Q^2$ (Pythagorean theorem)
- $P = S cos(phi)$
- $Q = S sin(phi)$
- $cos(phi) = P/S$ (Power Factor)
|
JEE Focus: Understanding the power triangle is crucial for solving complex problems involving multiple loads and for power factor correction.
---
###
5. Importance and Applications of Power Factor
A low power factor (i.e., $phi$ is large, $cosphi$ is small) is generally undesirable in AC systems. Here's why:
1.
Increased Current: For a given amount of real power (P) to be delivered to a load, if the power factor ($cosphi$) is low, the total current ($I_{rms} = P / (V_{rms} cosphi)$) drawn from the source will be higher.
2.
Higher IยฒR Losses: Increased current leads to greater heat losses (IยฒR losses) in the transmission lines, transformers, and other electrical equipment. This means less efficiency and wasted energy.
3.
Larger Equipment Rating: Generators, transformers, and transmission lines must be rated to handle the apparent power ($S = V_{rms} I_{rms}$). A low power factor means higher apparent power for the same real power, requiring larger and more expensive equipment.
4.
Voltage Regulation: Poor power factor can lead to larger voltage drops in the transmission and distribution lines, affecting the voltage stability at the consumer end.
5.
Penalties from Utilities: Industrial consumers with low power factors are often charged penalties by electricity providers because they demand more reactive power, which needs to be supplied by the utility, increasing infrastructure costs for the utility.
####
Power Factor Correction
To improve efficiency and avoid penalties, industrial and commercial consumers often implement
power factor correction. This usually involves connecting
capacitors in parallel with inductive loads (like motors, transformers, fluorescent lamps) which are the primary source of low, lagging power factor.
* Inductors consume
lagging reactive power.
* Capacitors provide
leading reactive power.
By connecting appropriate capacitors, the leading reactive power supplied by the capacitors cancels out some of the lagging reactive power demanded by the inductive loads, effectively reducing the net reactive power requirement from the source. This reduces the phase angle ($phi$) and brings the power factor ($cosphi$) closer to unity (1).
CBSE vs. JEE Focus:
*
CBSE: Basic definition of power factor, formula $P_{avg} = V_{rms} I_{rms} cosphi$, and general understanding that a high power factor is good.
*
JEE: Deep understanding of Apparent, Real, and Reactive Power, Power Triangle, calculation of power factor (R/Z), phase angle for various circuits (R, L, C, RL, RC, RLC), implications of low power factor, and principles of power factor correction. Expect problems involving calculation of the capacitance needed to improve power factor.
---
###
6. Solved Examples
Let's solidify our understanding with a couple of examples.
Example 1: Calculating Power for an LCR Series Circuit
An LCR series circuit has a resistance $R = 40 , Omega$, an inductive reactance $X_L = 90 , Omega$, and a capacitive reactance $X_C = 60 , Omega$. It is connected to an AC source of $V_{rms} = 200 , V$. Calculate:
(a) The impedance of the circuit.
(b) The RMS current in the circuit.
(c) The power factor.
(d) The average power consumed by the circuit (Real Power).
(e) The apparent power.
(f) The reactive power.
Solution:
(a)
Impedance (Z):
$Z = sqrt{R^2 + (X_L - X_C)^2}$
$Z = sqrt{(40 , Omega)^2 + (90 , Omega - 60 , Omega)^2}$
$Z = sqrt{(40)^2 + (30)^2}$
$Z = sqrt{1600 + 900}$
$Z = sqrt{2500}$
$Z = 50 , Omega$
(b)
RMS Current ($I_{rms}$):
$I_{rms} = frac{V_{rms}}{Z}$
$I_{rms} = frac{200 , V}{50 , Omega}$
$I_{rms} = 4 , A$
(c)
Power Factor ($cos phi$):
$cos phi = frac{R}{Z}$
$cos phi = frac{40 , Omega}{50 , Omega}$
$cos phi = 0.8$ (lagging, since $X_L > X_C$)
(d)
Average Power (Real Power, P):
$P = V_{rms} I_{rms} cos phi$
$P = (200 , V) (4 , A) (0.8)$
$P = 800 imes 0.8$
$P = 640 , W$
(e)
Apparent Power (S):
$S = V_{rms} I_{rms}$
$S = (200 , V) (4 , A)$
$S = 800 , VA$
(Check: $P = S cos phi Rightarrow 640 = 800 imes 0.8$, consistent!)
(f)
Reactive Power (Q):
First, find $phi$: $cos phi = 0.8 implies phi = arccos(0.8) approx 36.87^circ$.
Then, $sin phi = sin(36.87^circ) approx 0.6$.
$Q = V_{rms} I_{rms} sin phi$
$Q = (200 , V) (4 , A) (0.6)$
$Q = 480 , VAR$
(Check with Power Triangle: $S^2 = P^2 + Q^2 Rightarrow 800^2 = 640^2 + 480^2 Rightarrow 640000 = 409600 + 230400 Rightarrow 640000 = 640000$, consistent!)
---
Example 2: Power Factor Correction
An industrial load draws $10 , kW$ of real power at a lagging power factor of $0.6$ from a $250 , V_{rms}$, $50 , Hz$ AC supply.
(a) Calculate the apparent power and reactive power drawn by the load.
(b) Calculate the total RMS current drawn by the load.
(c) A capacitor is connected in parallel with the load to improve the power factor to $0.9$ lagging. Calculate the new RMS current drawn from the supply.
Solution:
(a)
Apparent Power (S) and Reactive Power (Q) of the initial load:
Given Real Power $P = 10 , kW = 10000 , W$.
Initial Power Factor $cos phi_1 = 0.6$.
We know $P = S cos phi_1$.
$S = frac{P}{cos phi_1} = frac{10000 , W}{0.6}$
$S = 16666.67 , VA$
To find Reactive Power $Q_1$, we need $sin phi_1$.
$sin phi_1 = sqrt{1 - cos^2 phi_1} = sqrt{1 - (0.6)^2} = sqrt{1 - 0.36} = sqrt{0.64} = 0.8$.
$Q_1 = S sin phi_1 = (16666.67 , VA) imes 0.8$
$Q_1 = 13333.33 , VAR$ (lagging, as it's an inductive load)
(b)
Total RMS current drawn by the initial load ($I_{rms,1}$):
$S = V_{rms} I_{rms,1}$
$I_{rms,1} = frac{S}{V_{rms}} = frac{16666.67 , VA}{250 , V}$
$I_{rms,1} = 66.67 , A$
(c)
New RMS current after power factor correction:
The real power $P$ consumed by the load remains the same ($10 , kW$) because the capacitor does not consume real power. It only supplies reactive power.
New Power Factor $cos phi_2 = 0.9$.
New Apparent Power $S_2 = frac{P}{cos phi_2} = frac{10000 , W}{0.9}$
$S_2 = 11111.11 , VA$
New RMS current $I_{rms,2} = frac{S_2}{V_{rms}} = frac{11111.11 , VA}{250 , V}$
$I_{rms,2} = 44.44 , A$
Notice that by improving the power factor from $0.6$ to $0.9$, the total current drawn from the supply has significantly reduced from $66.67 , A$ to $44.44 , A$. This reduction in current leads to all the benefits mentioned earlier (lower losses, smaller equipment, etc.).
To complete the picture, let's calculate the required reactive power of the capacitor:
New $sin phi_2 = sqrt{1 - (0.9)^2} = sqrt{1 - 0.81} = sqrt{0.19} approx 0.4359$.
New Reactive Power $Q_2 = S_2 sin phi_2 = (11111.11 , VA) imes 0.4359 approx 4843.95 , VAR$.
The reduction in reactive power supplied by the source is $Delta Q = Q_1 - Q_2 = 13333.33 - 4843.95 = 8489.38 , VAR$.
This is the leading reactive power that the capacitor must supply.
So, $Q_{capacitor} = 8489.38 , VAR$.
---
This detailed understanding of power in AC circuits and the power factor is crucial for not just theoretical physics problems but also for practical electrical engineering applications. Master these concepts for a strong foundation in electromagnetism!